PRODUCT CATALOG
Automatic digital current controller RTA-TS

Drawing No. |none

Automatic digital current controller RTA-TS

Automatic digital current controller RTA-TS with a power supply voltage detector. Climatic modification as per GOST Standard 15150-69 conforms to the 3rd UHLZ category.

FEATURES

  • accumulator bench voltage pattern: by 6 Accumulator benches – 12 V, by 7 -14 V

  • current controller output current peak value is: with the use of rectifying device VAK 13-2,1 A mark; with trafo POBS-2А mark — 10 А

  • equipping changes Accumulator bench mode of operation by itself and gives constant-current charge or boost charge mode signal by voltage pattern shown in the following list:

Operation LED «MODE»
condition
 Outdoor supervisory relay state Voltage pattern, V
Accumulator benches number
6 7
Operation 1
light on 12,00 ± 0,30 14,00 ± 0,30
Operation 2
flickering off 14,40 ± 0,30 16,80 ± 0,30
Operation 3  flickering off 13,2 ± 0,35 15,4 ± 0,35

Operation 1 - boost charge powering 
Operation 2 - boost charge deenergizing, constant-current charge powering 
Operation 3 - constant-current charge

Product details when in operation:

  • insulant system head between elements which carry electrical current as well as body by normal weather conditions

  • current controller size is 282×132×233

  • weight is max 4 kg

  • climatic modification as per GOST Standard 15150-69 conforms to the 3rd UHLZ category; operating temperature range from - 40º С to + 65º С, by relative air humidity 95% at the temperature 35º С.

  • on mechanical exposure feedback controller belongs to classification society МS2 per branch standard 32.146-2000

DESCRIPTION

Automatic digital current controller RTA-TS (in collaboration with rectifying device VAK 13 and trafo POBS-2А) are used for Accumulator bench charging rate corrective action in 2 modes: constant-current charge and boost charge. The device is a modernized analogy of current controllers PТА, RТА1 and is used as PТА, RТА1 changing.

Hardware details:

  • threshold switching setting between constant-current charge and boost charge modes is not needed

  • power supply voltage detector (at constant-current charge and boost charge modes startup)

  • simplified connection circuit

  • is totally compatible with the current technique

Component parts:

  • automatic digital current controller RTA-TS equipment – 1 pcs.

  • engineering instruction (1 pcs per 10 devices or less, sent to one receiver)

  • label (1 pcs per a device)